Deemed-to-Satisfy Provision · NCC 2025 Volume Three
B5D4 Fire-fighting water service
Part B5 Cross-connection control · NCC 2019: B5.4
Each fire-fighting water service must—
be assigned a Hazard Rating in accordance with B5D7(13) and B5D7(14); and
be isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed in accordance with AS/NZS 3500.1.
Changed since NCC 2022. See NCC 2022 Volume Three B5D4, or show what changed.
Each fire-fighting water service must — be assigned a Hazard Rating in accordance with S41C7; B5D7(13) and B5D7(14); and be isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed in accordance with Section 4 of AS/NZS 3500.1.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Can't meet B5D4? A Performance Solution must meet the Performance Requirements it satisfies: B5P1. Start a Performance Solution →