Deemed-to-Satisfy Provision · NCC 2025 Volume Three

B5D7 Cross-connection hazards

Part B5 Cross-connection control

Open B5D7 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) The Hazard Ratings prescribed for the cross-connection hazards described in (4) to (14) must be used for selecting the required backflow protection for the purposes of compliance with B5D2, B5D3, B5D4, B5D5 and B5D6.

(2) Cross-connection hazards within the site must be rated in accordance with—

(4), (5) and (6) for individual protection at the point of each individual hazard; or

(7), (8) and (9) for zone protection at the point where a group of hazards can be isolated.

(3) The hazard posed by the site to the Network Utility Operator ’s drinking water supply must be rated for containment protection in accordance with (10), (11) and (12).

(4) The following are Low Hazard for the purpose of individual protection:

Carbonated drink dispensing machines.

Drinking fountains and bottle fillers.

Coils and jackets in heat exchangers, in sealed and non-toxic environments only.

Drink dispensing equipment including vending machines and coffee machines.

External hose taps, with no hazards within 18 m.

Fixtures used for ablutions including baths, basins, showers and bidettes with a minimum 25 mm air gap.

Toilet douche seats where the outlet in all positions is at least 25 mm above the overflow level of the pan.

Fixtures used for food preparation, including sinks.

Flexible hoses used over domestic waste fixtures.

Haemodialysis machines in Class 1, Class 2 and Class 10 buildings.

Hair salon basins or troughs.

In-line water softeners and filters.

Photographic processing machines without developer mixing.

Emergency eye wash and shower stations for use with drinking water.

Food preparation or food storage tanks, vats or vessels (without clean-in-place systems).

(5) The following are Medium Hazard for the purpose of individual protection;

Chemical dispensers (low toxicity).

Dental consoles.

(6) The following are High Hazard for the purpose of individual protection:

Chlorinators.

Coils and jackets in heat exchangers, in unsealed and toxic environments.

Steam calorifiers.

Steam boilers.

Antibiotic injectors (agricultural).

Bidets and toilet douche seats where the outlet in any position is not 25 mm above the overflow level of the pan.

Bidettes installed without a minimum 25 mm air gap.

Handheld bidet/douche hoses and trigger sprays.

Chemical dispensers (high toxicity).

Cooling towers.

Demineralising equipment using ion-exchange resins with acid and alkali regeneration.

Equipment used for handling, mixing, measuring and processing chemical and microbiological substances.

Fogging and cleaning sprays with chemical injection or additives.

Mixing of chemicals.

Pan washing apparatus.

Photographic developers with drinking water supply rinse tanks or mixing facilities.

Plants with auxiliary non-drinking water supplies.

Type D irrigation system injected with fertilisers, herbicides, nematicides, insecticides or weedicides.

Weed and pest spraying and water cartage tasks.

Portable and mobile tankers.

Placenta/surgical waste disposal units.

Food preparation or food storage tanks, vats or vessels (with clean-in-place systems).

Buried rainwater tank.

(7) The following are Low Hazard for the purpose of zone protection:

Fire-fighting water storage tanks without chemical additives.

Food storage tanks, vats or vessels.

Hair salon basins or troughs.

Type B irrigation systems.

Water filtration equipment.

(8) The following are Medium Hazard for the purpose of zone protection:

Type C irrigation systems.

Beauty spas and foot salons.

(9) The following are High Hazard for the purpose of zone protection:

Photographic laboratories.

Aircraft facilities.

Secondary school laboratories, including fume cupboards.

Dental and medical procedure rooms and equipment using drinking water.

Clean-in-place systems.

Commercial laundries.

Cooling or heating systems with recirculating water.

Dockside facilities.

Drinking nipples and troughs (agricultural).

Food preparation or food storage tanks, vats or vessels.

Vats and vessels (clean-in-place systems).

In a Class 9 building—

dissecting rooms; and

utility rooms which contain fixtures other than hand basins; and

operating theatres.

Industrial and teaching laboratories.

Industrial process water that has been recirculated.

Mortuary equipment used in funeral parlours, mortuaries and autopsy areas.

Sanitary dump points.

Tanks, vats or vessels associated with electroplating, degreasing, descaling, stripping, pickling, dipping or the like.

Type D irrigation systems injected with fertilisers, herbicides, nematicides, insecticides or weedicides.

(10) The following are Low Hazard for the purpose of containment protection:

A water service provided to a Class 1, Class 2, Class 7a or Class 10 building where—

not more than 12 persons reside; and

the building may only use non-commercial amounts of cleaning products.

Premises served by a rainwater harvesting system, not including any rainwater storage tanks that are buried rainwater tanks.

A water service where there are no non-drinking water services within the property.

(11) The following are Medium Hazard for the purpose of containment protection:

A water service provided to a Class 3, Class 4, Class 5, Class 6 or Class 7b building where chemicals are not stored.

A water service provided to a property that has—

other non-drinking water services; or

a separate fire-fighting water service not directly connected to Network Utility Operator's water supply as mentioned in B5D7(13)(a)(i).

(12) The following are High Hazard for the purpose of containment protection:

A water service provided to a Class 7b building where chemicals may be stored.

A water service provided to a Class 8 or Class 9 building.

A water service provided to a property used for commercial agriculture, farming, turf irrigation, industrial, processing or chemical industries.

A water service provided to a property that has non-drinking water services from multiple sources with potential for health related contamination.

(13) The following fire-fighting water services are Low Hazard:

A fire-fighting water service which has—

a direct connection to a Network Utility Operator's water supply; and

does not contain a tank, reservoir, connection to another water supply, antifreeze or other additives, or fire brigade booster connection from an auxiliary water supply.

Domestic fire sprinkler systems installed in Class 1 buildings.

FPAA101D fire sprinkler systems.

(14) Any fire-fighting water services not referred to in (13) are Medium Hazard.

Notes

For B5D7(13) and B5D7(14), fire hose reels located within an area where a cross-connection hazard exists have a Hazard Rating the same as the areas within reach of the hose.

Exemptions

B5D7(10)(b) does not apply to a non-drinking water service provided to the property by a Network Utility Operator as part of a dual water supply.

B5D7(11)(b)(i) does not apply to a non-drinking water service provided to the property by a Network Utility Operator.

Applications

For B5D7(11), Medium Hazard properties for the purposes of containment protection include the following:

Caravan parks.

Food and beverage processing plants.

Premises that are connected to a grey water re-use system or a reticulated and disinfected reclaimed water system.

Public swimming pools.

For B5D7(12), High Hazard properties for the purpose of containment protection include the following:

Abattoirs.

Car and plant washing facilities.

Chemical laboratories.

Chemical plants.

Factories using, processing or manufacturing toxic chemicals.

Hospitals, mortuaries, dental surgeries, clinics or day surgeries and the like containing patient care areas such as an operating theatre, minor procedures consultation room, resuscitation, intensive care and coronary care.

Metal finishing plants.

Pathology laboratories.

Petroleum processing and storage plants and facilities.

Piers, docks, marinas and other waterfront facilities.

Premises where access to conduct inspections is restricted.

Sanitary depots.

Sewerage treatment plants and sewerage lift stations.

Universities.

Premises containing

New in NCC 2025. No B5D7 in NCC 2022 Volume Three; it may have moved or been renumbered.
Can't meet B5D7? A Performance Solution must meet the Performance Requirements it satisfies: B5P1. Start a Performance Solution →