Specification clause · NCC 2025 Volume Three
S2C16 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — walls
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 7.1
In walls fabricated of gypsum-perlite or gypsum-vermiculite plaster on metal lath and channel—
the lath must be securely wired to each side of 19 mm x 0.44 kg/m steel channels (used as studs) spaced at not more than 400 mm centres; and
the gypsum-perlite or gypsum-vermiculite plaster must be applied symmetrically to each exposed side of the lath.
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three S2C16.