Specification clause · NCC 2025 Volume Three
S2C17 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — columns
Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 7.2
(1) For the fire protection of steel columns with gypsum-perlite or gypsum-vermiculite on metal lath—
the lath must be fixed at not more than 600 mm centres vertically to steel furring channels, and—
if the plaster is to be 35 mm thick or more — at least 12 mm clear of the column; or
if the plaster is to be less than 35 mm thick — at least 6 mm clear of the column; or
the plaster may be applied to self-furring lath with furring dimples to hold it not less than 10 mm clear of the column.
(2) For the purposes of (1), the thickness of the plaster must be measured from the back of the lath.
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three S2C17.