SA B5D3 Non-drinking water service
SA Part B5 Cross-connection control · varies B5D3 Non-drinking water service
Delete clause B5D3 and insert SA B5D3 as follows:
(1) A hazard exists wherever it is possible for water or contaminants to enter a non-drinking water service or supply via any potential or actual cross-connection between itself and another separate non-drinking water service on the same site.
(2) Each hazard must—
be assigned a Hazard Rating in accordance with B5D7(10), B5D7(11) or B5D7(12); and
be isolated from the non-drinking water service by appropriate protection which is selected and installed in accordance with AS/NZS 3500.1.
(3) If a drinking water service is interconnected with a non-drinking water service for the purpose of emergency backup or to supplement, the drinking water supply shall be fitted with a high hazard backflow prevention device at the point of interconnection as a zone protection.