Table · NCC 2025 Volume Three
Table B5V1a Building class
Part B5 Cross-connection control
| Site condition | Common examples | Notes | Score |
|---|---|---|---|
| The property to which the water service is installed contains a Class 1, 2, 7a, or 10 building where not more than 12 people reside. | Domestic residences and carparks with no associated activities. | Building may use small amounts of cleaning products, etc. | 1 |
| The property to which the water service is installed contains a Class 3, 4, 5, 6 or 7b building where chemical products are not stored. | Hostel, hotel and multi-level office. | Building is likely to have greater than 12 residents and/or occupants, and may contain moderate amounts of cleaning or commercial chemicals. | 2 |
| The property to which the water service is installed contains a Class 7b, 8 or 9 building where chemical products are stored. | Mechanical workshop, metal finisher, cleaning product wholesaler. | May contain large amounts of hazardous or toxic commercial chemicals. | 3 |
Table for B5V1 Determination of individual and zone hazard ratings
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table B5V1a.