Table B5V1a Building class

Part B5 Cross-connection control

Open Table B5V1a on NCC Online ↗
Site conditionCommon examplesNotesScore
The property to which the water service is installed contains a Class 1, 2, 7a, or 10 building where not more than 12 people reside.Domestic residences and carparks with no associated activities.Building may use small amounts of cleaning products, etc.1
The property to which the water service is installed contains a Class 3, 4, 5, 6 or 7b building where chemical products are not stored.Hostel, hotel and multi-level office.Building is likely to have greater than 12 residents and/or occupants, and may contain moderate amounts of cleaning or commercial chemicals.2
The property to which the water service is installed contains a Class 7b, 8 or 9 building where chemical products are stored.Mechanical workshop, metal finisher, cleaning product wholesaler.May contain large amounts of hazardous or toxic commercial chemicals.3

Table for B5V1 Determination of individual and zone hazard ratings

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table B5V1a.

Defined terms used