Table · NCC 2025 Volume Three
Table B5V1b On-site water services
Part B5 Cross-connection control
| Site condition | Common examples | Notes | Score |
|---|---|---|---|
| There is only a drinking water supply and no other water sources to the property. | The drinking water source may be a rainwater tank connected to a detached dwelling. | Residential rainwater tanks are considered drinking water. | 0 |
| There is one drinking water supply and potentially other non-drinking water supplies or a separate fire-fighting water service available to the property (not applicable if the non-drinking water supply is Network Utility Operator provided recycled water with a sewerage source). | Network Utility Operator drinking water supply and a separate fire water service. | Network Utility Operator supplied recycled water with a sewerage source is assessed separately due to greater health risks. | 3 |
| Commercial agriculture, farming, turf irrigation, industrial, processing or chemical industries. The property is supplied with drinking water and non-drinking water from multiple sources with potential for health related contamination. | Property has a Network Utility Operator drinking water source and an on-site wastewater effluent irrigation system, process water or bore water source. | Increased potential for cross-connection between drinking water and non-drinking water with high consequences such as chemicals, recycled sewerage, medical or biological contaminants. | 5 |
Table for B5V1 Determination of individual and zone hazard ratings
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table B5V1b.