Table · NCC 2025 Volume Three

Table B5V1b On-site water services

Part B5 Cross-connection control

Open Table B5V1b on NCC Online ↗
Site conditionCommon examplesNotesScore
There is only a drinking water supply and no other water sources to the property.The drinking water source may be a rainwater tank connected to a detached dwelling.Residential rainwater tanks are considered drinking water.0
There is one drinking water supply and potentially other non-drinking water supplies or a separate fire-fighting water service available to the property (not applicable if the non-drinking water supply is Network Utility Operator provided recycled water with a sewerage source).Network Utility Operator drinking water supply and a separate fire water service.Network Utility Operator supplied recycled water with a sewerage source is assessed separately due to greater health risks.3
Commercial agriculture, farming, turf irrigation, industrial, processing or chemical industries. The property is supplied with drinking water and non-drinking water from multiple sources with potential for health related contamination.Property has a Network Utility Operator drinking water source and an on-site wastewater effluent irrigation system, process water or bore water source.Increased potential for cross-connection between drinking water and non-drinking water with high consequences such as chemicals, recycled sewerage, medical or biological contaminants.5

Table for B5V1 Determination of individual and zone hazard ratings

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three Table B5V1b.

Defined terms used