Western Australia variation · NCC 2025 Volume Three

WA C2D4 General requirements

WA Part C2 Sanitary drainage systems · varies C2D4 General requirements

Open on NCC Online ↗

Delete clause C2D4 and insert WA C2D4 as follows:

A sanitary drainage system must be in accordance with AS/NZS 3500.2 with the following variations:

For clause 3.8.2 Delete paragraph (b) and insert:

(b) the drains laid through footings shall be installed with an annular space of not less than 25 mm filled with a liner of flexible material. However, the drains need not be installed in such a way if the drains are installed in a building that is—

classified as a Class 1a or 10a building under Volume 1 and 2 of the National Construction Code; and

in sandy soil classified as Class ‘A’ within the meaning of AS 2870-2011 (Residential slabs and footings).

For clause 3.18 delete paragraph (d) and insert:

(d) A vacuum sewer system DN 100 downstream vent shall be connected on the main drain—

before or on the inspection shaft riser; and

after the last fixture on the main drain.

The vacuum sewer system DN 100 downstream vent should be connected as close as possible to the inspection shaft riser.

(e) Vacuum sewer system and boundary trap low level vents shall terminate between a minimum of 150 mm and a maximum of 250 mm above ground or adopted flood level using one of the following methods—

one 88° bend and a flat grate with invert level not less than 150 mm above ground or adopted flood level;

two 88° bends and a flat grate or vent cowl so that there is not less than 150 mm between the flat grate or vent cowl and the ground or adopted flood level;

an air admittance valve not less than 150 mm above ground or adopted flood level installed in accordance with Clause 6.9.

For clause 4.5.3 delete paragraph (b) and at the end of the clause insert:

However, if the reflux valve is being installed in relation to an existing building, the reflux valve may be installed upstream from the inspection shaft.

For clause 4.6.2 delete paragraph (b) and insert:

(b)have each gully riser provided with a grating or cover of a loose; pop-out type to relieve surcharge and allow adequate ventilation to the gully riser; and

For clause 4.6.2 in paragraph (c)(ii) delete “surround).’ and insert

surround); and

For clause 4.6.2 at the end of the clause insert:

(d) in relation to a class 1a or class 10a building within the meaning of Volume 1 and 2 of the National Construction Code — have the height of the gully riser not more than 600 mm measured from the top of the water seal to the grate of the gully.

For Table 4.6.6.6 delete the table and insert:

See Table 4.6.6.6.

For clause 4.7.1 delete paragraph (c) and insert:

(c) on the downstream end of any branch drain that exits a building, between the building and the junction into the main drain;

For clause 6.5.1 delete the clause and insert:

6.5.1 General

Each sanitary fixture and appliance must have a self-sealing device or trap.

A self-sealing device must—

be in the same room as the fixture or appliance that it serves; and

be accessible.

A trap (other than a self-sealing device) must—

be in the same room as the fixture or appliance that it serves; and

be accessible unless the trap is in the ground or concrete.

A trap (other than a self-sealing device) in the ground or concrete must not have—

a loose coupling nut; or

a diameter that is greater than the diameter of the outlet for the fixture or appliance that the trap serves.

A trap (other than a self-sealing device) that is in the ground or concrete must be directly below the outlet for the fixture or appliance that the trap serves.

For clause 13.9 delete the passage that begins with “if” and continues to the end of the clause.

Table 4.6.6.6 Point of measurement on fixtures for height above overflow gully

Fixture

Point of measurement

Floor waste gully

Top surface level of the grate

All other fixtures (including greywater diversion devices)

Overflow level of the fixture

New in NCC 2025. No WA C2D4 in NCC 2022 Volume Three; it may have moved or been renumbered.

The national clause

Other states and territories