VIC C2D4 General requirements
VIC Part C2 Sanitary drainage systems · varies C2D4 General requirements
Delete clause C2D4 and insert VIC C2D4 as follows:
(1) A sanitary drainage system must be in accordance with AS/NZS 3500.2; subject to the following—
insert Clause 4.4.2.1(e):
4.4.2.1(e) Where an inspection shaft or boundary trap riser in a below ground sanitary drainage system is not subject to Clause 4.4.2.1(c), a light cover must be installed in a visible location and have the top of the riser protected from damage (e.g. by concrete or similar means of protection).
insert Clause 4.6.2(d):
4.6.2(d) Have risers installed vertically with no offsets.
replace clause 5.3(c) with:
5.3(c) Under all bends greater than DN 65 to vertical risers.
replace Clause 5.4.2(d) with:
5.4.2(d) Free running sand, excavated from the trench, capable of passing through a 2 mm mesh sieve, which does not contain clay, organic or other deleterious materials.
After 15.1, insert Clause 15.1(A) as follows:
15.1(A) Testing of a sanitary drainage installation.
If installed at a property provided with non-drinking water by the Network Utility Operator, testing of a sanitary drainage installation may be carried out in accordance with—
a water test using non-drinking water provided by the Network Utility Operator in accordance with clause 15.2; or
an air test in accordance with clause 15.3; or
vacuum test in accordance with clause 15.4; or
in cases other than in (a), testing may be carried out by way of—
an air test in accordance with clause 15.3; or
a vacuum test in accordance with clause 15.4.
Insert Clause 3.2A after Clause 3.2 as follows:
3.2A Standards for laying of below ground sanitary drains.
Where a below ground sanitary drain is unable to comply with Clause 3.2 of AS/NZS 3500.2, the below-ground sanitary drainage must:
be laid as a straight line of drain with no branches or changes in direction; and
be constructed of a material that complies with the requirements in Section 2 of AS/NZS 3500.2; and
have inspection openings with shafts terminating at the finished surface level, installed in permanently accessible positions, in the open air at the upstream entry and downstream exit points.
(2) Insert Clause 3.10.3.1 after Clause 3.10.3 as follows:
Clause 3.10.3.1 Discharge pipes measuring DN 50 or smaller must not be installed in a below ground sanitary drainage system, except for discharge pipes connected to floor waste gullies or vertical riser from a graded drain.
Changed since NCC 2022. See NCC 2022 Volume Three VIC C2D4, or show what changed.
Delete clause C2D4 and insert VIC C2D4 as follows: (1) … AS/NZS 3500.2; subject to the following — insert Clause 4.4.2.1(e): (e) 4.4.2.1(e) Where an inspection shaft or boundary trap riser in a below ground sanitary drainage system is located clear of a building and is not likely subject to be damaged by vehicular traffic, Clause 4.4.2.1(c), a light cover must be installed in accordance with clause 4.4.2.1(a) a visible location and clause 4.4.2.1(c)(ii) and (iii). have the top of the riser protected from damage (e.g. by concrete or similar means of protection). insert Clause 4.6.2(d): (d) 4.6.2(d) Have risers installed vertically with no offsets. replace clause 5.3(c) of AS/NZS 3500.2 is varied so that concrete support used to support drains must be provided to support with: 5.3(c) Under all bends greater than DN 65 to vertical risers. replace Clause 5.4.2(d) with: 5.4.2(d) Free running sand, excavated from the trench, capable of passing … which does not contain clay, organic or other deleterious materials. Insert After 15.1, insert Clause 15.1(b) 15.1(A) as follows: 15.1(A) Testing of a sanitary drainage installation. If installed at a … 15.3; or a vacuum test in accordance with clause 15.4. Insert Clause 3.2A after Clause 3.2 as follows: 3.2A Standards for laying of below ground sanitary drains. Where a below ground sanitary drain is unable to comply with Clause 3.2 of AS/NZS 3500.2, the below-ground sanitary drainage must: be laid as a straight line of drain with no branches or changes in direction; and be constructed of a material that complies with the requirements in Section 2 of AS/NZS 3500.2; and have inspection openings with shafts terminating at the finished surface level, installed in permanently accessible positions, in the open air at the upstream entry and downstream exit points. (2) Insert Clause 3.10.3.1 after Clause 3.10.3 as follows: Clause 3.10.3.1 Discharge pipes measuring DN 50 or smaller must not be … floor waste gullies or vertical riser from a graded drain.
Removed words are struck through; added words are highlighted. Comparison of the text only.
The national clause
Other states and territories
- WA Delete clause C2D4 and insert WA C2D4 as follows: A sanitary drainage system must be in accordance with AS/NZS 3500.2…
- NSW Delete clause C2D4 and insert NSW C2D4 as follows: A sanitary drainage system must be in accordance with AS/NZS 3500.2…
- SA Delete clause C2D4 and insert SA C2D4 as follows: A sanitary drainage system must be in accordance with AS/NZS 3500.2…
- TAS Insert TAS subclause C2D4(2) in clause C2D4 as follows: (2) For Tasmanian venting requirements see TAS C2D6.