Performance Requirement · NCC 2025 Volume Two
H4P4 Lighting
Part H4 Health and amenity · NCC 2019: P2.4.4
(1) A habitable room must be provided with windows, where appropriate to the function or use of that part of the building, so that natural light, when available, provides an average daylight factor of not less than 2%.
(2) Artificial lighting must be installed to provide an illuminance of not less than 20 lux appropriate to the function or use of the building to enable safe movement by occupants.
Applications
H4P4(2) only applies—
to sanitary compartments, bathrooms, shower rooms, airlocks, laundries and the like; and
if natural light of a suitable standard is not available.
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H4P4.