NSW H3D2 Fire hazard properties and non-combustible building elements
NSW Part H3 Fire safety · varies H3D2 Fire hazard properties and non-combustible building elements
Delete clause H3D2 and insert NSW H3D2 as follows:
(1) The following materials, though combustible or containing combustible fibres, may be used wherever a non-combustible material is required:
Plasterboard.
Perforated gypsum lath with a normal paper finish.
Fibrous-plaster sheet.
Fibre-reinforced cement sheeting
Pre-finished metal sheeting having a combustible surface finish not exceeding 1 mm thick and where the Spread-of-Flame Index of the product is not more than 0.
Sarking-type materials that do not exceed 1 mm in thickness and have a Flammability Index not greater than 5.
Bonded laminated materials where—
each lamina, including any core, is non-combustible; and
each adhesive layer does not exceed 1 mm in thickness and the total thickness of the adhesive layers does not exceed 2 mm; and
the Spread-of-Flame Index and the Smoke-Developed Index of the bonded laminated material as a whole do not exceed 0 and 3 respectively.
(2) The fire hazard properties, and determination thereof, of materials used in a Class 1 building, including floor or ceiling spaces common with a Class 10 building, must comply with the following:
Sarking-type materials used in the roof must have a Flammability Index not greater than 5.
Flexible ductwork used for the transfer of products initiating from a heat source that contains a flame must comply with the fire hazard properties set out in AS 4254.1.