New South Wales variation · NCC 2025 Volume Two

NSW H3D2 Fire hazard properties and non-combustible building elements

NSW Part H3 Fire safety · varies H3D2 Fire hazard properties and non-combustible building elements

Open on NCC Online ↗

Delete clause H3D2 and insert NSW H3D2 as follows:

(1) The following materials, though combustible or containing combustible fibres, may be used wherever a non-combustible material is required:

Plasterboard.

Perforated gypsum lath with a normal paper finish.

Fibrous-plaster sheet.

Fibre-reinforced cement sheeting

Pre-finished metal sheeting having a combustible surface finish not exceeding 1 mm thick and where the Spread-of-Flame Index of the product is not more than 0.

Sarking-type materials that do not exceed 1 mm in thickness and have a Flammability Index not greater than 5.

Bonded laminated materials where—

each lamina, including any core, is non-combustible; and

each adhesive layer does not exceed 1 mm in thickness and the total thickness of the adhesive layers does not exceed 2 mm; and

the Spread-of-Flame Index and the Smoke-Developed Index of the bonded laminated material as a whole do not exceed 0 and 3 respectively.

(2) The fire hazard properties, and determination thereof, of materials used in a Class 1 building, including floor or ceiling spaces common with a Class 10 building, must comply with the following:

Sarking-type materials used in the roof must have a Flammability Index not greater than 5.

Flexible ductwork used for the transfer of products initiating from a heat source that contains a flame must comply with the fire hazard properties set out in AS 4254.1.

New in NCC 2025. No NSW H3D2 in NCC 2022 Volume Two; it may have moved or been renumbered.