NT H6V2 Verification using a reference building
NT Part H6 Energy efficiency · varies H6V2 Verification using a reference building
Insert NT clause H6V2 in clause H6V2 as follows:
(1) Compliance with NT H6P1 is verified when a proposed building—
when compared with a reference building has—
in climate zone 1, a cooling load equal to or less than that of the reference building; or
in climate zones 3, a heating load and a cooling load equal to or less than that of the reference building.
(2) The heating load and cooling load for the proposed building and the reference building must be determined using the same—
thermal calculation method; and
location specific data, including that of climate and topography appropriate to the location where the proposed building is to be constructed if the data is available, or the nearest location with similar climatic conditions in the same climate zone for which the data is available; and
impact of adjoining structures and features; and
soil conditions; and
orientation; and
floor plan, including the location of glazing; and
number of storeys; and
solar absorptance of external surfaces; and
roof cladding; and
separating walls; and
external non-glazed doors; and
intermediate floors; and
floor coverings; and
internal zones; and
internal heat gains including people and appliances.
(3) The thermal calculation method used must be capable of assessing the heating load and cooling load by modelling—
the building fabric; and
glazing and shading; and
air infiltration and ventilation; and
the function and use of the building including zoning, hours of occupation, hours of heating and cooling availability and internal heat gains; and
space temperature settings in the range 20ºC to 21ºC for heating and 25ºC to 28ºC for cooling; and
relevant built-environment and topographical features; and
the sensible heat component of the cooling load and heating load.
(4) Climatic data employed in the thermal calculation method must be based on hourly recorded values and be representative of a typical year for the proposed location.
(5) The reference building must comply with the Deemed-to-Satisfy Provisions in the following parts of the ABCB Housing Provisions—
NT Part 13.2 for the building fabric; and
NT Part 13.3 for the external glazing and shading; and
NT Part 13.4 for building sealing; and
NT Part 13.5 for air movement.
Changed since NCC 2022. See NCC 2022 Volume Two NT H6V2, or show what changed.