Specification clause · NCC 2025 Volume Two

S2C18 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — beams

Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 7.3

Open S2C18 on NCC Online ↗

For the fire protection of steel beams with gypsum-perlite or gypsum-vermiculite on metal lath—

the lath must be fixed at not more than 600 mm centres to steel furring channels and at least 20 mm clear of the steel; and

the thickness of the plaster must be measured from the back of the lath.

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two S2C18.