NCC 2025 Volume Two
Specification 2 Descriptions of elements referred to in Specification 1
29 clauses · Open on NCC Online ↗
- S2C1 ScopeThis Specification sets out the descriptions of elements referred to in Tables S1C2a, S1C2b, S1C2c, S1C2e, S1C2f, S1C2g, S1C2h, S1C2i, S1C2j, S1C2l…
- S2C2 Mortar for masonryMasonry units of ashlar, calcium silicate, concrete or fired clay (including terracotta blocks) must be laid in cement mortar or composition mortar…
- S2C3 Gypsum blocksGypsum blocks must be laid in gypsum-sand mortar or lime mortar.
- S2C4 Gypsum-sand mortar and plasterGypsum-sand mortar and gypsum-sand plaster must consist of either— not more than 3 parts by volume of sand to 1 part by volume of gypsum; or if lime…
- S2C5 Gypsum-perlite and gypsum-vermiculite plasterGypsum-perlite or gypsum-vermiculite plaster must be applied— in either one or 2 coats each in the proportions of 1 m3 of perlite or vermiculite to…
- S2C6 Plaster of cement and sand or cement, lime and sandPlaster prescribed in Tables S1C2c, S1C2e, S1C2f, S1C2g, S1C2h, S1C2i, S1C2j, S1C2l and S1C2m — must consist of cement and sand or cement, lime and…
- S2C7 Plaster reinforcementIf plaster used as fire protection on walls is more than 19 mm thick— it must be reinforced with expanded metal lath that— has a mass per unit area…
- S2C8 Ashlar stone masonryAshlar masonry must not be used in a part of the building containing more than 2 storeys, and must not be of— aplite, granite, granodiorite, quartz…
- S2C9 Dimensions of masonryThe thicknesses of masonry of calcium-silicate, concrete and fired clay are calculated as set out in S2C10 to S2C12.
- S2C10 Solid unitsFor masonry in which the amount of perforation or coring of the units does not exceed 25% by volume (based on the overall rectangular shape of the…
- S2C11 Hollow unitsFor masonry in which the amount of perforation or coring of the units exceeds 25% by volume (based on the overall rectangular shape of the unit) the…
- S2C12 Equivalent thicknessThe equivalent thickness of a masonry unit is calculated by dividing the net volume by the area of one vertical face.
- S2C13 Height-to-thickness ratio of certain wallsThe ratio of height between lateral supports to overall thickness of a wall of ashlar, no-fines concrete, unreinforced concrete, solid gypsum…
- S2C14 Increase in thickness by plastering — wallsIf a wall of ashlar, solid gypsum blocks or concrete is plastered on both sides to an equal thickness, the thickness of the wall for the purposes of…
- S2C15 Increase in thickness by plastering — columnsWhere Tables S1C2e, S1C2f, S1C2g, S1C2h, S1C2i and S1C2j indicate that column-protection is to be plastered, the tabulated thicknesses are those of…
- S2C16 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — wallsIn walls fabricated of gypsum-perlite or gypsum-vermiculite plaster on metal lath and channel— the lath must be securely wired to each side of 19 mm…
- S2C17 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — columnsFor the fire protection of steel columns with gypsum-perlite or gypsum-vermiculite on metal lath— the lath must be fixed at not more than 600 mm…
- S2C18 Gypsum-perlite or gypsum-vermiculite plaster or metal lath — beamsFor the fire protection of steel beams with gypsum-perlite or gypsum-vermiculite on metal lath— the lath must be fixed at not more than 600 mm…
- S2C19 Exposure of columnsA column incorporated in or in contact on one or more sides with a wall of solid masonry or concrete at least 100 mm thick may be considered to be…
- S2C20 Exposure of beamsA beam, open-web joist, girder or truss in direct and continuous contact with a concrete slab or a hollow block floor or roof may be considered to…
- S2C21 Filling of column spacesThe spaces between the fire-protective material and the steel (and any re-entrant parts of the column itself) must be filled solid with a…
- S2C22 Hollow terracotta blocksThe proportion of cored holes or perforations in a hollow terracotta block (based on the overall rectangular volume of the unit) must not exceed the…
- S2C23 Reinforcing for column and beam protection — masonryMasonry of calcium-silicate, fired clay and concrete for the protection of steel columns must have steel-wire or mesh reinforcement in every second…
- S2C24 Reinforcing for column and beam protection — gypsum blocks and hollow terracotta blocksGypsum blocks and hollow terracotta blocks for the protection of steel columns must have steel-wire or mesh reinforcement in every course and lapped…
- S2C25 Reinforcing for column and beam protection — structural concrete and poured gypsumIf a steel column or a steel beam is to be protected with structural concrete or poured gypsum, the concrete or gypsum must be reinforced with…
- Table S2C26a Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with H or I cross-sectionSurface to be protected | Reinforcement required if smaller dimension of surface exceeds (mm) | Max spacing of fixings of the mesh to surface (mm)…
- Table S2C26b Reinforcement of gypsum-perlite or gypsum-vermiculite plaster sprayed to contour — vertical members with other shapesSurface to be protected | Reinforcement required if smaller dimensions of surface exceeds (mm) | Max spacing of fixings of the mesh to surface (mm)…
- S2C26 Reinforcing for column and beam protection — gypsum-perlite or gypsum-vermiculite plaster sprayed to contourIf a steel column or steel beam is protected with either gypsum-perlite or gypsum-vermiculite plaster sprayed to contour and the construction falls…
- S2C27 Measurement of thickness of column and beam protectionThe thickness of the fire protection to steel columns and steel beams (other than fire protection of gypsum-perlite or gypsum-vermiculite plaster…