Specification clause · NCC 2025 Volume Two

S2C7 Plaster reinforcement

Specification 2 Descriptions of elements referred to in Specification 1 · NCC 2019: Sch. 5 (Annex): 1.6

Open S2C7 on NCC Online ↗

If plaster used as fire protection on walls is more than 19 mm thick—

it must be reinforced with expanded metal lath that—

has a mass per unit area of not less than 1.84 kg/m2; and

has not fewer than 98 meshes per metre; and

is protected against corrosion by galvanising or other suitable method; or

it must be reinforced with 13 mm x 13 mm x 0.7 mm galvanised steel wire mesh securely fixed at a distance from the face of the wall of not less than ⅓ of the total thickness of the plaster.

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two S2C7.