South Australia variation · NCC 2025 Volume Two

SA H8D2 Livable housing design

SA Part H8 Livable housing design · varies H8D2 Livable housing design

Open on NCC Online ↗

Delete clause H8D2 and insert SA H8D2 as follows:

(1) A Class 1a dwelling must comply with the ABCB Standard for Livable Housing Design.

(2) Clause 1.1 of the ABCB Standard for Livable Housing Design need not be complied with if—

step-free access via an appurtenant garage, carport or parking space in accordance with Clause 1.1(1)(b) or (c) is not provided; and

one or more of the following conditions exist:

The average slope of the ground on which the access path would be constructed exceeds a gradient of 1:14.

To provide an external step-free access path would necessitate construction of ramping that exceeds the length and gradient allowed by Clause 1.1(4).

There is insufficient space available on the allotment on which to construct a step-free access path complying with Clause 1.1.

Subject to (3), the difference in level, measured vertically from the pedestrian entry at the allotment boundary or parking space to the floor level at the entrance door on the nearest floor containing habitable rooms, would necessitate construction of ramping that exceeds the length and gradient allowed under Clause 1.1(4).

(3) For the purposes of (2)(b)(iv), the difference in level must be measured from the floor level at the entrance door, or if there is an attached deck, balcony or the like that provides a step-free connection to the entrance door, from the lowest point of that deck, balcony or the like above the surface beneath.

(4) Even if Clause 1.1 is not complied with, all other relevant provisions of the ABCB Standard for Livable Housing Design must still be complied with.

(5) Clause 2.2 Threshold of the ABCB Standard for Livable Housing Design, is varied as follows:

The threshold of an entrance door that is subject to Clause 2.1 must—

be level; or

have a sill height not more than 5 mm if the lip is rounded or bevelled; or

have a ramped threshold that—

does not extend internally beyond the depth of the door jamb; and

has a gradient not steeper than 1:8; and

is at least as wide as the minimum clear opening width of the entrance door; and

does not intrude into the minimum dimensions of a landing area that is required by Clause 2.3; or

where the requirements of (a), (b) or (c) cannot meet the weatherproofing requirements of the NCC, for external entrance doors containing a raised door or sill—

have no lip or upstand greater than 15 mm within the sill profile; and

have no more than 5 mm height difference between the edge of the top surface of the sill and the adjoining finished surface.

(6) The sanitary compartment subject to Clause 4.1 of the ABCB Standard for Livable Housing Design may be located on either—

the ground or entry level; or

the lowest level containing a habitable room within a Class 1a building.

(7) The hobless and step-free entry required by Clause 5.2 of the ABCB Standard for Livable Housing Design—

to an enclosed shower area must have—

a water bar with a maximum height of 5 mm installed above and sealed to the waterstop at the shower area entry; or

a linear drain at the shower area entry.

to an unenclosed shower area must comply with AS 3740 or Part 10.2 of the ABCB Housing Provisions.

Notes

Enclosed shower areas and unenclosed shower areas that are hobless and step-free must be waterproofed in accordance with AS 3740 or Part 10.2 of the ABCB Housing Provisions.

New in NCC 2025. No SA H8D2 in NCC 2022 Volume Two; it may have moved or been renumbered.

The national clause