Western Australia variation · NCC 2025 Volume Two

WA H9D4 Heated water use efficiency

WA Part H9 Water use

Open on NCC Online ↗

Delete clause H9D4 and insert WA H9D4 as follows:

(1) All internal heated water outlets (such as taps, showers and washing machine water supply fittings) must be connected to a heated water system or a recirculating heated water system with pipes installed and insulated in accordance with AS/NZS 3500: Plumbing and Drainage, Part 4 Heated Water Services.

(2) The pipe from the heated water system or recirculating heated water system to the furthest heated water outlet must not be more than 20 m in length or 2 litres of internal volume.

Changed since NCC 2022. See NCC 2022 Volume Two WA H9D4, or show what changed.

Delete clause H9D4 and insert WA H9D4 as follows: (1) All internal heated water outlets (such as taps, showers … 20 m in length or 2 litres of internal volume.

Removed words are struck through; added words are highlighted. Comparison of the text only.