Verification Method · NCC 2025 Volume One
C1V2 Fire spread between buildings on the same allotment
Part C1 Fire resistance · NCC 2019: CV2
Compliance with C1P2(1)(c) to avoid the spread of fire between buildings on the same allotment is verified when, for the distances between buildings set out in Column 1 of Table C1V2, it is calculated that a building—
is capable of withstanding the heat flux set out in Column 2 of Table C1V2 without ignition; and
will not cause heat flux in excess of those set out in Column 2 of Table C1V2.
Table C1V2 Fire spread between buildings on the same allotment
Column 1 (Distance between buildings on the same allotment (m))
Column 2 (Heat flux (kW/m2))
0
80
2
40
6
20
12
10
Tables
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C1V2.