Table C1V2 Fire spread between buildings on the same allotment
| Column 1 (Distance between buildings on the same allotment (m)) | Column 2 (Heat flux (kW/m2)) |
|---|---|
| 0 | 80 |
| 2 | 40 |
| 6 | 20 |
| 12 | 10 |
Table for C1V2 Fire spread between buildings on the same allotment
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table C1V2.