C3D11 Separation of lift shafts
Part C3 Compartmentation and separation · NCC 2019: C2.10
(1) Any lift connecting more than 2 storeys, or more than 3 storeys if the building is sprinklered, (other than lifts which are wholly within an atrium) must be separated from the remainder of the building by enclosure in a shaft in which—
in a building required to be of Type A construction — the walls have the relevant FRL prescribed by Specification 5; and
in a building required to be of Type B construction — the walls—
if load bearing, have the relevant FRL prescribed by Table S5C21e; or
if non-load bearing, be of non-combustible construction.
(2) Any lift in a patient care area in a Class 9a health-care building or a resident use area in Class 9c building must be separated from the remainder of the building by a shaft having an FRL of not less than—
in a building of Type A or B construction — 120/120/120; or
in a building of Type C construction — 60/60/60.
(3) An emergency lift must be contained within a fire-resisting shaft having an FRL of not less than 120/120/120.
(4) Openings for lift landing doors and services must be protected in accordance with the Deemed-to-Satisfy Provisions of Part C4.