Deemed-to-Satisfy Provision · NCC 2025 Volume One

D2D17 Non-required stairways, ramps or escalators

Part D2 Provision for escape · NCC 2019: D1.12

Open D2D17 on NCC Online ↗

An escalator, moving walkway or non-required non fire-isolated stairway or pedestrian ramp—

must not be used between storeys in—

a patient care area in a Class 9a health-care building; or

a resident use area in a Class 9c building; and

may connect any number of storeys if it is—

in an open spectator stand or indoor sports stadium; or

in a carpark or an atrium; or

outside a building; or

in a Class 5 or 6 building that is sprinklered throughout, where the escalator, walkway, stairway or ramp complies with Specification 14; and

except where permitted in (b) must not connect more than—

3 storeys if—

each of those storeys is provided with a sprinkler system (other than a FPAA101D system) complying with Specification 17 throughout; and

at least one of those storeys is situated at a level at which there is a direct egress to a road or open space; or

2 storeys, provided that those storeys are consecutive, and one of the storeys is situated at a level at which there is direct egress to a road or open space; and

except where permitted in (b) or (c), must not connect, directly or indirectly, more than 2 storeys at any level in a Class 5, 6, 7, 8 or 9 building and those storeys must be consecutive.

New in NCC 2025. No D2D17 in NCC 2022 Volume One; it may have moved or been renumbered.