D2D17 Non-required stairways, ramps or escalators
Part D2 Provision for escape · NCC 2019: D1.12
An escalator, moving walkway or non-required non fire-isolated stairway or pedestrian ramp—
must not be used between storeys in—
a patient care area in a Class 9a health-care building; or
a resident use area in a Class 9c building; and
may connect any number of storeys if it is—
in an open spectator stand or indoor sports stadium; or
in a carpark or an atrium; or
outside a building; or
in a Class 5 or 6 building that is sprinklered throughout, where the escalator, walkway, stairway or ramp complies with Specification 14; and
except where permitted in (b) must not connect more than—
3 storeys if—
each of those storeys is provided with a sprinkler system (other than a FPAA101D system) complying with Specification 17 throughout; and
at least one of those storeys is situated at a level at which there is a direct egress to a road or open space; or
2 storeys, provided that those storeys are consecutive, and one of the storeys is situated at a level at which there is direct egress to a road or open space; and
except where permitted in (b) or (c), must not connect, directly or indirectly, more than 2 storeys at any level in a Class 5, 6, 7, 8 or 9 building and those storeys must be consecutive.