D2D16 Horizontal exits
Part D2 Provision for escape · NCC 2019: D1.11
(1) Horizontal exits must not be counted as required exits —
between sole-occupancy units; or
in a Class 9b building used as an early childhood centre, primary or secondary school.
(2) In a Class 9a health-care building or Class 9c building, horizontal exits may be counted as required exits if the path of travel from a fire compartment leads by one or more horizontal exits directly into another fire compartment which has at least one required exit which is not a horizontal exit.
(3) In cases other than in (2), horizontal exits must not comprise more than half of the required exits from any part of a storey divided by a fire wall.
(4) Horizontal exits must have a clear area on the side of the fire wall to which occupants are evacuating, to accommodate the total number of persons (calculated under D2D18) served by the horizontal exit of not less than—
2.5 m2 per patient/resident in a Class 9a health-care building or Class 9c aged care building; and
0.5 m2 per person in any other case.
(5) Where a fire compartment is provided with only two exits, and one of those exits is a horizontal exit, the clear area required by (4) is to be of a size that accommodates all the occupants from the fire compartment being evacuated.
(6) In a Class 9b early childhood centre, the clear area required by (4) must accommodate all occupants of the early childhood centre.
(7) The clear area required by (4) must be connected to the horizontal exit by an unobstructed path that has at least the dimensions required for the horizontal exit and may include the area of the unobstructed path.
(8) Each fire compartment required by C3D6(2) must be served by not less than 2 horizontal exits, each located not less than 9 m from—
at least one other horizontal exit; and
an exit other than a horizontal exit.