D3D4 Non-fire-isolated stairways and ramps

Part D3 Construction of exits · NCC 2019: D2.3

Open D3D4 on NCC Online ↗

In a building having a rise in storeys of more than 2, required stairs and ramps (including landings and any supporting building elements) which are not required to be within a fire-resisting shaft, must be constructed according to D3D3, or only of—

reinforced or prestressed concrete; or

steel in no part less than 6 mm thick; or

timber that—

has a finished thickness of not less than 44 mm; and

has an average density of not less than 800 kg/m3 at a moisture content of 12%; and

has not been joined by means of glue unless it has been laminated and glued with resorcinol formaldehyde or resorcinol phenol formaldehyde glue.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D3D4.
Can't meet D3D4? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →