Deemed-to-Satisfy Provision · NCC 2025 Volume One
E1D11 Where sprinklers are required: Class 9b buildings
Part E1 Fire fighting equipment · NCC 2019: Table E1.5
(1) In a Class 9b building, other than an early childhood centre, see Part I1.
(2) In a Class 9b early childhood centre and in a building containing a Class 9b early childhood centre, sprinklers are required throughout the whole building, including any part of another class.
Exemptions
E1D11(2) does not apply to a Class 9b early childhood centre —
wholly within a storey that provides direct egress to a road or open space; or
with a rise in storeys of not more than 2, where the Class 9b early childhood centre is the only use in the building.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E1D11.
Can't meet E1D11? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →