Part E1 Fire fighting equipment
26 clauses · Open on NCC Online ↗
- E1O1 ObjectiveThe Objective of this Part is to— safeguard occupants from illness or injury while evacuating during a fire; and provide facilities for occupants…
- E1F1 Fire-fighting equipmentA building is to be provided with fire-fighting equipment to safeguard against fire spread— to allow occupants time to evacuate safely without being…
- E1P1 Fire hose reelsA fire hose reel system must be installed to the degree necessary to allow occupants to safely undertake initial attack on a fire appropriate to—…
- E1P2 Fire extinguishersFire extinguishers must be installed to the degree necessary to allow occupants to undertake initial attack on a fire appropriate to— the function…
- E1P3 Fire hydrantsA fire hydrant system must be provided to the degree necessary to facilitate the needs of the fire brigade appropriate to— fire-fighting operations;…
- E1P4 Automatic fire suppression systemsAn automatic fire suppression system must be installed to the degree necessary to control the development and spread of fire appropriate to— the…
- E1P5 Fire-fighting services in buildings under constructionSuitable means of fire-fighting must be installed to the degree necessary in a building under construction to allow initial fire attack by…
- E1P6 Fire control centresSuitable facilities must be provided to the degree necessary in a building to co-ordinate fire brigade intervention during an emergency appropriate…
- E1V1 Fire Safety Verification MethodCompliance with E1P1, E1P2, E1P3, E1P4 and E1P6 is verified when a building is designed in accordance with C1V4.
- E1D1 Deemed-to-Satisfy Provisions SA TASWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements E1P1 to E1P6 are satisfied by complying with— E1D2 to E1D17; and in a…
- E1D2 Fire hydrantsA fire hydrant system must be provided to serve a building— having a total floor area greater than 500 m2; and where a fire brigade station is— no…
- E1D3 Fire hose reelsE1D3 does not apply to— a Class 2, 3 or 5 building or Class 4 part of a building; or a Class 8 electricity network substation; or a Class 9c…
- E1D4 SprinklersA sprinkler system must— be installed in a building or part of a building when required by E1D5 to E1D13 as applicable; and comply with…
- E1D5 Where sprinklers are required: all classificationsSprinklers are required throughout the whole building if any part of the building has an effective height of more than 25 m. Exemptions E1D5 does…
- E1D6 Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings VICIn a Class 2 or 3 building, or any multi-classified building containing a Class 2 or 3 part, sprinklers are required throughout the whole building…
- E1D7 Where sprinklers are required: Class 3 building used as a residential care buildingSprinklers are required throughout— a Class 3 building used as a residential care building; and any fire compartment containing a Class 3 part used…
- E1D8 Where sprinklers are required: Class 6 buildingIn a Class 6 building, sprinklers are required in fire compartments where either of the following apply: A floor area of more than 3 500 m2. A…
- E1D9 Where sprinklers are required: Class 7a buildingIn a Class 7a building, other than an open-deck carpark which is a separate building, sprinklers are required in fire compartments where— more than…
- E1D10 Where sprinklers are required: Class 9a health-care building used as a residential care building and Class 9c buildings NTIn a Class 9a health-care building used as a residential care building, sprinklers are required throughout the building and in any fire compartment…
- E1D11 Where sprinklers are required: Class 9b buildingsIn a Class 9b building, other than an early childhood centre, see Part I1. (2) In a Class 9b early childhood centre and in a building containing a…
- E1D12 Where sprinklers are required: additional requirementsFor sprinkler requirements for atriums, see Part G3. (2) For sprinkler requirements for large isolated buildings, see C3D4.
- E1D13 Where sprinklers are required: occupancies of excessive hazardIn occupancies of excessive hazard, sprinklers are required in fire compartments where either of the following apply: A floor area of more than 2…
- E1D14 Portable fire extinguishersPortable fire extinguishers must be— provided as listed in (3) and (4); and for a Class 2, 3 or 5 building or Class 4 part of a building, provided—…
- E1D15 Fire control centresA fire control centre facility in accordance with Specification 19 must be provided for— a building with an effective height of more than 25 m; and…
- E1D16 Fire precautions during constructionIn a building under construction— not less than one fire extinguisher to suit Class A, B and C fires and electrical fires must be provided at all…
- E1D17 Provision for special hazards TASSuitable additional provision must be made if special problems of fighting fire could arise because of— the nature or quantity of materials stored,…