E3D8 Accessible features required for passenger lifts
Part E3 Lift installations · NCC 2019: Table E3.6a, Table E3.6b
In an accessible building, every passenger lift must have the following features where applicable:
A handrail complying with the provisions for a mandatory handrail in AS 1735.12 for all lifts except—
a stairway platform lift; and
a low-rise platform lift.
Lift floor dimensions of not less than 1400 mm wide x 1600 mm deep for all lifts which travel more than 12 m.
Lift floor dimensions of not less than 1100 mm wide x 1400 mm deep for all lifts which travel not more than 12 m, except a stairway platform lift.
Lift floor dimensions of not less than 810 mm wide x 1200 mm deep for a stairway platform lift.
Minimum clear door opening complying with AS 1735.12 for all lifts except a stairway platform lift.
Passenger protection system complying with AS 1735.12 for all lifts with power-operated doors.
Lift landing doors at the upper landing for all lifts except a stairway platform lift.
Lift car and landing control buttons complying with AS 1735.12 for all lifts except—
a stairway platform lift; and
a low-rise platform lift.
Lighting in accordance with AS 1735.12 for all enclosed lift cars.
For all lifts serving more than 2 levels—
automatic audible information within the lift car to identify the level each time the car stops; and
audible and visual indication at each lift landing to indicate the arrival of the lift car; and
audible information and audible indication required by (i) and (ii) is to be provided in a range of between 20 - 80 dB(A) at a maximum frequency of 1500 Hz.
Emergency hands-free communication, including a button that alerts a call centre of a problem and a light to signal that the call has been received, for all lifts except a stairway platform lift.