Deemed-to-Satisfy Provision · NCC 2025 Volume One

F2D3 Rooms containing urinals

Part F2 Wet areas and overflow protection · NCC 2019: F1.7(c), (d) and (e)

Open F2D3 on NCC Online ↗

(1) Where a slab or stall type urinal is installed—

the floor surface of the room containing the urinal must be an impervious material; and

where no step is installed, must—

be graded to the urinal channel for a distance of 1.5 m from the urinal channel; and

have the remainder of the floor graded to a floor waste; and

where a step is installed—

the step must have an impervious surface and be graded to the urinal channel; and

the floor behind the step must be graded to a floor waste; and

the junction between the floor surface and the urinal channel must be impervious.

(2) Where a wall hung urinal is installed—

the wall must be surfaced with impervious material extending from the floor to not less than 50 mm above the top of the urinal and not less than 225 mm on each side of the urinal; and

the floor must be surfaced with an impervious material and be graded to a floor waste.

(3) In a room with timber or steel-framed walls and containing a urinal—

the wall must be surfaced with an impervious material extending from the floor to not less than 100 mm above the floor surface; and

the junction of the floor surface and the wall surface must be impervious.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F2D3.
Can't meet F2D3? A Performance Solution must meet the Performance Requirements it satisfies: F2P1, F2P2. Start a Performance Solution →