Deemed-to-Satisfy Provision · NCC 2025 Volume One
F2D4 Floor wastes
Part F2 Wet areas and overflow protection · NCC 2019: SA F1.11, F1.11
Varied in SA. Check the variation for your state.
(1) In a Class 2 or 3 building or Class 4 part of a building, a bathroom or laundry located at any level above a sole-occupancy unit or public space must have a floor waste.
(2) Where a floor waste is installed—
the minimum continuous fall of a floor plane to the waste must be 1:80; and
the maximum continuous fall of a floor plane to the waste must be 1:50.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F2D4.
Can't meet F2D4? A Performance Solution must meet the Performance Requirements it satisfies: F2P1, F2P2. Start a Performance Solution →