Verification Method · NCC 2025 Volume One
F4V1 Sanitary facilities
Part F4 Sanitary and other facilities · NCC 2019: FV2.1
(1) Compliance with F4P1, for the number of sanitary facilities, is verified when queuing modelling predicts that occupant waiting time for sanitary facilities is at least equivalent to the waiting time predicted using the respective Deemed-to-Satisfy Provisions.
(2) For calculations performed under (1), the occupant waiting time is determined as the 90th percentile wait time at maximum population.
(3) Queuing modelling in (1) must reflect the following:
Function or use of the building.
Number and gender of occupants.
The disability or other particular needs of the occupants.
Occupant usage patterns.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F4V1.