Performance Requirement · NCC 2025 Volume One
F7P4 Sound transmission through walls in a residential care building
Part F7 Sound transmission and insulation · NCC 2019: NT FP5.4, FP5.5
Varied in NT. Check the variation for your state.
(1) A wall separating sole-occupancy units, or a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room, including the effect of services and their penetrations, must minimise the transmission of—
airborne sound such that the wall has a weighted standardised level difference (DnT,w) not less than 40; and
impact generated sound, if the wall separates a sole-occupancy unit from a kitchen or laundry.
(2) Sound insulation required by (1) must be sufficient to prevent illness or loss of amenity to the occupants.
Applications
F7P4 only applies to a Class 9c building.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F7P4.