G1D3 Refrigerated chambers, strong-rooms and vaults
Part G1 Minor structures and components · NCC 2019: G1.2
(1) A refrigerated or cooling chamber, strongroom or vault that is of sufficient size for a person to enter must have—
a door which is capable of being opened by hand from inside without a key; and
internal lighting controlled only by a switch which is located adjacent to the entrance doorway inside the chamber, strongroom or vault; and
an indicator lamp positioned outside the chamber, strongroom or vault which is illuminated when the interior lights required by (b) are switched on; and
an alarm that is—
located outside but controllable only from within the chamber, strongroom or vault; and
able to achieve a sound pressure level outside the chamber, strongroom or vault of 90 dB(A) when measured 3 m from the sounding device.
(2) A door required by (1)(a) in a refrigerated or cooling chamber must have a doorway with a clear width of not less than 600 mm and a clear height not less than 1.5 m.