Deemed-to-Satisfy Provision · NCC 2025 Volume One

G4D7 Fire-fighting services and equipment

Part G4 Construction in alpine areas · NCC 2019: G4.8

Open G4D7 on NCC Online ↗

(1) Every Class 2, 3, 5, 6, 7, 8 or 9 building must have—

a manually operated fire alarm system with call-points complying with AS 1670.1; and

fire hydrants installed in accordance with E1D2(2); and

fire hose reels installed in accordance with E1D3(2) to (7), except that in a Class 2 or 3 building—

for the purpose of E1D3(2), a sole-occupancy unit is considered to be a fire compartment; and

for the purpose of E1D3(3)(b), a sole-occupancy unit may be served by a single fire hose reel located at the level of egress from that sole-occupancy unit; and

for the purpose of E1D3(6), a fire hose may pass through a doorway in bounding construction referred to in C4D12.

(2) The requirements of (1)(c) do not apply to a Class 8 electricity network substation.

New in NCC 2025. No G4D7 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet G4D7? A Performance Solution must meet the Performance Requirements it satisfies: G4P1, G4P2, G4P3, G4P4. Start a Performance Solution →