New South Wales variation · NCC 2025 Volume One

NSW

NSW Specification 7 Fire hazard properties

Open on NCC Online ↗

Material or assembly location

Flammability Index

Spread-of-Flame Index

Smoke-Developed Index

Fire control rooms subject to Specification 19 and fire-isolated exits, other than a sarking-type material used in a ceiling or used as an attachment or part of an attachment to a building element. Note 1

N/A

0

2

Class 9b buildings used as an entertainment venue, a material used to cover closed back upholstered seats in any part available to the public—where smoking is permitted; or flame is exposed in connection with the preparation of meals Note 4

N/A

6

5

Class 9b buildings used as an entertainment venue, a material used as a curtain, blind or similar decor in any part available to the public. Notes 4 and 5

6

N/A

N/A

Class 9b buildings used as an entertainment venue, a material used to form a cinematograph screen. Notes 4, 5 and 6

12

0

7

Class 9b buildings used as a public hall or the like: A proscenium curtain required by Specification 32.

N/A

0

3

Escalators, moving walkways or non-required non fire-isolated stairways or pedestrian ramps subject to Specification 14.

N/A

0

5

Sarking-type materials: In a fire control room subject to Specification 19 or a fire-isolated exit used in the form of an exposed wall or ceiling.

0

N/A

N/A

Sarking-type materials other than in a fire control room subject to Specification 19 or a fire-isolated exit used in the form of an exposed wall or ceiling. Note 2

5

N/A

N/A

Other materials or locations and insulation materials other than Sarking-type materials. Notes 2 and 3

N/A

9

8 if the Spread-of-Flame Index is more than 5

Note

In a fire control room or fire-isolated stairway, a material used as an attachment or part of an attachment to a building element must, if combustible, be attached directly to a non-combustible substrate and not exceed 1 mm finished thickness.

A material, other than one located within a fire-isolated exit or fire control room, may be covered on all faces by concrete or masonry not less than 50 mm thick, as an alternative to meeting the specified indices.

In the case of a composite member or assembly, the member or assembly must be constructed so that when assembled as proposed in a building—

any material which does not comply with this Table is protected on all sides and edges from exposure to the air; and

the member or assembly, when tested in accordance with Specification 3, has a Spread-of-Flame Index and Smoke-Developed Index not exceeding those prescribed in this Table; and

the member or assembly retains the protection in position so that it prevents ignition of the material and continues to screen it from access to free air for a period of not less than 10 minutes.

Any fire-retardant coating used in an entertainment venue to make a material comply with a required Flammability Index, Spread-of-Flame Index or Smoke-Developed Index must be certified by—

its manufacturer or distributor—

as approved for use with the fabric to achieve the required indices; and

to retain its retardancy effect after a minimum of 5 commercial dry cleaning or laundering operations carried out in accordance with AS 2001.5.4, Procedure 7A, using non-phosphate ECE reference detergent A (without optical brightener); and

the applicator as having been carried out in accordance with the manufacturer’s specification.

Materials used in an entertainment venue must have a label affixed to a representative sample of each different material indicating, in legible characters—

name of manufacturer; and

trade name and description of material’s composition; and

retardant treatment (if any), name of applicator and date of application; and

AS 1530 Part 2 and/or AS/NZS 1530 Part 3 test number and its Flammability Index, Spread-of-Flame Index and Smoke-Developed Index; and

approved methods of cleaning.

A cinematograph screen must have a supporting frame of metal construction.

User group

Facility type

Design occupancy

Number

Male patrons

Closet pans

1 - 100

1

101 - 300

2

>300

Add 1 per 200

Urinals

1 - 50

1

51 - 100

2

101 - 150

3

151 - 200

4

201 - 250

5

>250

Add 1 per 100

Washbasins

1 - 50

1

51 - 200

2

>200

Add 1 per 200

Female patrons

Closet pans

1 - 25

1

26 - 50

2

51 - 100

3

101 - 150

4

151 - 200

5

201 - 250

6

>250

Add 1 per 100

Washbasins

1 - 50

1

51 - 150

2

>150

Add 1 per 200

Note

Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 20.

Sanitary facilities need not be provided for patrons in a small live music or arts venue that is not a licensed premises.

Changed since NCC 2022. See NCC 2022 Volume One NSW, or show what changed.

Material or assembly location Flammability Index Spread-of-Flame Index Smoke-Developed Index … cinematograph screen must have a supporting frame of metal construction. Type of use Area per person Art gallery, exhibition area, museum 4 m2 Auditorium — bench seating 450 mm/person Auditorium — fixed seating count seats Auditorium — removable seating 1 m2 Auditorium — standing area 0.5 m2 Bar — standing 0.5m2 Bar — other 1 m2 Board room 2 m2 Boarding house 15 m2 Cafe, church, dining room 1 m2 Carpark 30 m2 Computer room 25 m2 Court room — judicial area 10 m2 Court room — public seating 1 m2 Dance floor 0.5 m2 Dormitory 5 m2 Early childhood centre 4 m2 Entertainment venue — other than auditorium 1.2 m2 Factory — machine shop, fitting shop or like place for cutting, grading, finishing or fitting of metals or glass, except in the fabrication of structural steelwork or manufacture of vehicles or bulky products 5 m2 Factory — areas used for fabrication and processing other than a machine shop, fitting shop or the like 50 m2 Factory — a space in which the layout and natural use of fixed plant or equipment determines the number of persons who will occupy the space during working hours Area per person determined by the use of the plant or equipment Gymnasium 3 m2 Hostel, hotel, motel, guest house 15 m2 Indoor sports stadium —arena 10 m2 Kiosk 1 m2 Kitchen, laboratory, laundry 10 m2 Library — reading space 2 m2 Library — storage space 30 m2 Office, including one for typewriting or document copying 10 m2 Patient care areas 10 m2 Plant room —ventilation, electrical or other service units 30 m2 Plant room — boilers or power plant 50 m2 Reading room 2 m2 Restaurant 1 m2 School — general classroom 2 m2 School — multi-purpose hall 1 m2 School — staff room 10 m2 School — trade and practical area — primary 4 m2 School — trade and practical area — secondary As for workshop Shop — space for sale of goods — at a level entered direct from the open air or any lower level 3 m2 Shop — space for sale of goods — all other levels 5 m2 Showroom — display area, covered mall or arcade 5 m2 Skating rink, based on rink area 1.5 m2 Small live music or arts venue – dance floor 0.5 m2 Small live music or arts venue – Information and education facility 4 m2 Small live music or arts venue – other 1 m2 Spectator stand, audience viewing area — standing viewing area 0.3 m2 Spectator stand, audience viewing area — removable seating 1 m2 Spectator stand, audience viewing area — fixed seating Per number of seats Spectator stand, audience viewing area — bench seating 450 mm/person Storage space 30 m2 Swimming pool, based on pool area 1.5 m2 Switch room, transformer room 30 m2 Telephone exchange — private 30 m2 Theatre dressing room 4 m2 Transport terminal 2 m2 Workshop — for maintenance staff 30 m2 Workshop — for manufacturing processes As for factory Note Bar standing is an area used by the standing patrons and extends not less than 1.5 m wide from the outside edge of the bar top for the length of the serving area of the bar. User group Facility type Design occupancy Number Male patrons Closet … music or arts venue that is not a licensed premises.

Removed words are struck through; added words are highlighted. Comparison of the text only.