NSW B1P1 Structural reliability
NSW Part B1 Structural provisions · varies B1P1 Structural reliability
Delete clause B1P1 and insert NSW B1P1 as follows:
(1) By resisting the actions to which it may reasonably be expected to be subjected, a building or structure, during construction and use, with appropriate levels of reliability, must—
perform adequately under all reasonably expected design actions; and
withstand extreme or frequently repeated design actions; and
be designed to sustain local damage, with the structural system as a whole remaining stable and not being damaged to an extent disproportionate to the original local damage; and
avoid causing damage to other properties.
(2) The actions to be considered to satisfy (1) and (2) include but are not limited to—
permanent actions (dead loads) including, for a Class 7b building, an additional notional permanent roof load of not less than 0.15 kPa to support the addition of solar photovoltaic panels; and
imposed actions (live loads arising from occupancy and use); and
wind action; and
earthquake action; and
snow action; and
liquid pressure action; and
ground water action; and
rainwater action (including ponding action); and
earth pressure action; and
differential movement; and
time dependent effects (including creep and shrinkage); and
thermal effects; and
ground movement caused by—
swelling, shrinkage or freezing of the subsoil; and
landslip or subsidence; and
siteworks associated with the building or structure; and
construction activity actions; and
termite actions.
Exemptions
The requirement for an additional notional permanent roof load to support photovoltaic panels in NSW B1P1(3)(a) does not apply to a Class 7b building—
where 100% of the roof area is shaded for more than 70% of daylight hours; or
with a roof area of not more than 55 m2; or
where more than 50% of the roof area is used as a terrace, carpark, roof garden, roof light or the like.