New South Wales variation · NCC 2025 Volume One

NSW I4D15 Safety curtains

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

Delete clause I4D15 and insert NSW I4D15 as follows:

A safety curtain required by NSW I4D8 must—

be made of non-combustible material; and

be so fitted that, when it is closed, it forms an efficient smoke seal between the stage and the auditorium; and

be capable of withstanding a pressure differential of 0.5 kPa over its entire surface area; and

be run on steel guides located on each side of the proscenium opening; and

remain engaged in its guides if the guides, together with their fittings and attachments and that part of the curtain engaged in the guides, are subjected to a pressure differential of 1 kPa; and

be of sufficiently robust construction to withstand damage by scenery, stage properties and falling debris; and

be capable of closing the proscenium opening within 30 seconds, either by gravity slide or by motor assisted mechanisms; and

have manual controls, located on each side of the stage, for the closing of the curtains; and

have a notice displayed adjacent to the operating controls, in clear and legible letters and symbols of adequate size, indicating its use and operation; and

when operated, actuate a distinctive warning alarm audible to persons on the stage and must not be reliant for its operation solely on the primary electricity supply; and

have the words “Safety Curtain” exhibited on the curtain in clear and legible letters of adequate size to enable them to be read from all parts of the auditorium.

Changed since NCC 2022. See NCC 2022 Volume One NSW I4D15, or show what changed.