NSW I4D46 Projection suites: rooms to be provided
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D46 and insert NSW I4D46 as follows:
A projection suite in accordance with the staffing requirements of Section 72 of the Environmental Planning and Assessment Regulation 2021 must contain either—
a projection room and sanitary accommodation comprising at least 1 closet pan and 1 washbasin, where the projection suite is continually staffed; or
a projection room fitted with the following equipment—
an automatic fire suppression system in accordance with SSL Appraisal Specification FAS 102 or a sprinkler system complying with AS 2118; and
a smoke detection system which will—
comply with AS 1670.1; and
be connected to a fire station or other approved monitoring service where arrangements are in place to initiate fire brigade response; and
close down all shutters fitted to projection or observation ports; and
activate sufficient general lighting to provide a minimum of 40 lux measured at floor level in any auditorium affected; and
operate a public address system to automatically announce a suitable message from the management of the premises; and
activate an audible alarm to immediately indicate to management the presence of smoke in the projection room.