NSW I4D48 Projection suites: concession for protection of some openings
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D48 and insert NSW I4D48 as follows:
If a projection or observation port is not more than 0.1 m2 in area—
a metal shutter not less than 1.5 mm thick may be fitted thereto instead of the protection required under NSW C4D12; and
any metal shutter or protection system must be equipped with a device to permit the closing of the shutter or the protection system from easily accessible operating positions adjacent to each egress doorway from the projection room.