NSW I4D50 Basement storeys: more than two
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D50 and insert NSW I4D50 as follows:
If the entertainment venue includes more than 2 basement storeys —
the construction must be of at least Type B; and
all required exits from the basement must be enclosed in a fire-resisting shaft having an FRL as required by the relevant Type of construction; and
the building must be equipped with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
Changed since NCC 2022. See NCC 2022 Volume One NSW I4D50, or show what changed.
Delete clause I4D50 and insert NSW I4D50 as follows: If the entertainment venue includes more than 2 basement storeys … than a FPAA101D or FPAA101H system) complying with Specification 17.
Removed words are struck through; added words are highlighted. Comparison of the text only.