NSW I4D53 Electric mains installation: separate sub-mains
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D53 and insert NSW I4D53 as follows:
Where an entertainment venue has its mains supply in common with that of another building or where it is a part of a building—
the entertainment venue must be served by a separate and independent sub-main from the main switchboard; and
each sub-main, the consumer’s main and the supply authority’s conductors within the building must be protected against fire by means of—
mineral-insulated metal-sheathed cables or other cables that provide at least 2 hours’ fire protection; or
heavy-duty PVC conduit or metallic pipe, concrete encased in walls or slabs with a minimum of 50 mm cover; or
heavy-duty PVC conduit or metallic pipe, buried at least 500 mm below ground level, for underground cabling.
Changed since NCC 2022. See NCC 2022 Volume One NSW I4D53, or show what changed.
Delete clause I4D53 and insert NSW I4D53 as follows: Where an entertainment venue has its mains supply in common … at least 500 mm below ground level, for underground cabling.