NSW I4D55 Lighting: lighting levels

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

Delete clause I4D55 and insert NSW I4D55 as follows:

Where the lamps utilised in the general lighting are of a type that will not relight immediately after the restoration of the primary electricity supply to those lamps—

a time delay or other suitable means must be provided to maintain the emergency lighting for a period not less than that necessary to allow the general lighting lamps to restrike; or

lamps of a type that will provide immediate lighting must be installed and—

arranged in such a manner as to ensure visual conditions not inferior to those required to be provided by the emergency lighting; and

capable of being switched in common with the general lighting and of being controlled also by the override switch required by NSW I4D54(2).

Changed since NCC 2022. See NCC 2022 Volume One NSW I4D55, or show what changed.

Delete clause I4D55 and insert NSW I4D55 as follows: Where the lamps utilised in the general lighting are of … controlled also by the override switch required by NSW I4D54(2).