NSW I5D4 Exits to be provided
NSW Part I5 Temporary structures
Delete clause I5D4 and insert NSW I5D4 as follows:
Without limiting the generality of NSW I5D3 —
the number of exits to be provided for a temporary structure designed to accommodate a number of persons specified in Column 1 of NSW Table I5D4 must be not less than the number of exits specified in Column 2 of that Table in respect of that number of persons; and
the aggregate width of the exits to a temporary structure designed to accommodate a number of persons specified in Column 1 of NSW Table I5D4 must be not less than the width specified in Column 3 of that Table in respect of that number of persons.
Insert NSW table (I5D4) I5D4 as follows:
NSW Table I5D4: Number of exits and widths
Column 1: accommodation provided (persons)
Column 2: number of exits required
Column 3: Aggregate width of exits (mm)
1 - 25
1 - 2
1000
26 - 50
2
1500
51 - 75
2
2000
76 - 100
2
2500
101 - 200
2
3000
201 - 400
3
4500
401 - 600
4
6000
601 - 800
5
7500
801 - 1000
5
9000
Over 1000
5 exits plus one additional exit for each additional 450 persons, or part thereof.
9000 mm, plus 500 mm for each additional 50 persons or part thereof.
Table Notes
Where only one exit is provided that exit must be at least 1000 mm wide.
Where 2 exits are provided each must be at least 500 mm wide.
Changed since NCC 2022. See NCC 2022 Volume One NSW I5D4, or show what changed.
Delete clause I5D4 and insert NSW I5D4 as follows: Without limiting the generality of NSW I5D3 — the number … are provided each must be at least 500 mm wide.
Removed words are struck through; added words are highlighted. Comparison of the text only.