Specification clause · NCC 2025 Volume One

S12C5 Fire shutters

Specification 12 Fire doors, smoke doors, fire windows and shutters · NCC 2019: Spec C3.4: 4

Open S12C5 on NCC Online ↗

A required fire shutter must—

be a shutter that—

is identical with a tested prototype that has achieved the required FRL; and

is installed in the same manner and in an opening that is not larger than the tested prototype; and

did not have a rise in average temperature on the side remote from the furnace of more than 140 K during the first 30 minutes of the test; or

be a steel shutter complying with AS 1905.2 if a metallic fire shutter is not prohibited by C4D6.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S12C5.