S17C10 Anti-tamper devices
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 10
(1) Where a sprinkler system is installed—
over any stage area in a theatre, public hall or the like, visual and audible status indication of sprinkler valves must be provided at the location normally used by the stage manager; or
in a space housing lift electrical and control equipment (including machine rooms, secondary floors and sheave rooms), any valves provided to control sprinklers in these spaces must be located adjacent to the space.
(2) Any valves provided to control sprinklers required by (1) must be fitted with anti-tamper monitoring devices connected to a monitoring panel.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C10.