Specification clause · NCC 2025 Volume One

S17C11 Sprinkler systems in carparks

Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 11

Open S17C11 on NCC Online ↗

A sprinkler system protecting a carpark complying with S5C19(3) in a multi-classified building must—

be independent of the sprinkler system protecting any part of the building not used as a carpark; or

if forming part of a sprinkler system protecting a part of the building not used as a carpark, be designed such that the section protecting the non-carpark part can be isolated without interrupting the water supply or otherwise affecting the effective operation of the section protecting the carpark.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C11.

Clauses referred to