Specification clause · NCC 2025 Volume One

S17C14 Early childhood centres

Specification 17 Fire sprinkler systems

Open S17C14 on NCC Online ↗

Quick response sprinklers must be provided to a Class 9b early childhood centre required to have an automatic fire sprinkler system.

Limitations

S17C14 does not apply to a Class 9b early childhood centre —

wholly within a storey that provides direct egress to a road or open space; or

with a rise in storeys of not more than 2, where the Class 9b early childhood centre is the only use in that building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C14.

Defined terms used