S17C13 Sprinkler systems in lift installations

Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 13

Open S17C13 on NCC Online ↗

(1) Where sprinklers are installed in a space housing lift electrical and control equipment, including machine rooms, secondary floors and sheave rooms, sprinklers in these spaces must—

have heads protected from accidental damage by way of a guard that will not impair the performance of the head; and

be capable of being isolated and drained, either separately or collectively, without isolating any other sprinklers within the building.

(2) Valves provided to control sprinklers referred to in (1) must be installed in accordance with S17C10(2).

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C13.