S17C2 Application of automatic fire sprinkler standards

Specification 17 Fire sprinkler systems · NCC 2019: VIC Spec E1.5: 2, Spec E1.5: 2

Open S17C2 on NCC Online ↗

Subject to this Specification, an automatic fire sprinkler system must comply with—

for all building classifications: AS 2118.1; or

for a Class 2 or 3 building with an effective height of not more than 25 m and a rise in storeys of 4 or more: Specification 18 and the relevant provisions of this Specification as applicable; or

for Class 5, 6, 7, 8, 9a (other than a residential care building) or 9b (other than a Class 9b early childhood centre) parts of a building with an effective height not more than 25 m, which also contains Class 2 or 3 parts: a sprinkler system in accordance with Specification 18 as for a Class 2 or 3 building and the relevant provisions of this Specification except—

a FPAA101D sprinkler system cannot be used where the Class 5, 6, 7, 8, 9a (other than a residential care building) or 9b parts—

contain more than 2 storeys; or

are more than 25% of the total floor area of the building; or

are located above the fourth storey; and

a FPAA101D or FPAA101H sprinkler system cannot be used where the Class 7a part accommodates more than 40 vehicles; or

for a combined sprinkler and fire hydrant system: AS 2118.6; or

for a Class 9a health-care building used as a residential care building: AS 2118.4 as applicable; or

for a Class 2, 3 or 9c building: AS 2118.4 as applicable.

Changed since NCC 2022. See NCC 2022 Volume One S17C2, or show what changed.

Subject to this Specification, an automatic fire sprinkler system must … sprinkler system cannot be used where the Class 7a part (other than an open-deck carpark) accommodates more than 40 vehicles; or for a combined sprinkler … Class 2, 3 or 9c building: AS 2118.4 as applicable.

Removed words are struck through; added words are highlighted. Comparison of the text only.