Specification clause · NCC 2025 Volume One
S17C3 Separation of sprinklered and non-sprinklered areas
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 3
Where a part of a building is not protected with sprinklers, the sprinklered and non-sprinklered parts must be fire-separated with a wall or floor which must—
comply with any specific requirement of the Deemed-to-Satisfy Provisions of the BCA; or
where there is no specific requirement, comply with the relevant part of AS 2118, FPAA101D or FPAA101H.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S17C3.