Specification clause · NCC 2025 Volume One

S19C10 Size and contents of a fire control room

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 9

Open S19C10 on NCC Online ↗

(1) A fire control room must contain—

a Fire Indicator Panel and necessary control switches and visual status indication for all required fire pumps, smoke control fans and other required fire safety equipment installed in the building; and

a telephone connected to the telecommunications network; and

a blackboard or whiteboard not less than 1200 mm wide x 1000 mm high; and

a pin-up board not less than 1200 mm wide x 1000 mm high; and

a raked plan layout table of a size suitable for laying out the plans provided under (f); and

colour-coded, durable, tactical fire plans.

(2) In addition, a fire control room may contain—

master emergency control panels, lift annunciator panels, remote switching controls for gas or electrical supplies and emergency generator backup; and

building security, surveillance and management systems if they are completely segregated from all other systems.

(3) A fire control room must—

have a floor area of not less than 10 m2 and the length of any internal side must be not less than 2.5 m; and

if only the minimum prescribed equipment is installed — have a net floor area of not less than 8 m2 with a clear space of not less than 1.5 m2 in front of the Fire Indicator Panel; and

if additional equipment is installed — have an additional area of not less than 2 m2 net floor area for each additional facility and a clear space of not less than 1.5 m2 in front of each additional control or indicator panel; and

be constructed such that the area required for any path of travel through the room to other areas is provided in addition to the requirements (b) and (c).

Changed since NCC 2022. See NCC 2022 Volume One S19C10, or show what changed.

(1) A fire control room must contain — a Fire … fire safety equipment installed in the building; and a telephone directly connected to an external telephone exchange; the telecommunications network; and a blackboard or whiteboard not less than 1200 mm … is provided in addition to the requirements (b) and (c).

Removed words are struck through; added words are highlighted. Comparison of the text only.