Specification clause · NCC 2025 Volume One

S19C11 Ventilation and power supply for a fire control room

Specification 19 Fire control centres · NCC 2019: Spec E1.8: 10

Open S19C11 on NCC Online ↗

(1) A fire control room must be ventilated by—

natural ventilation from a window or doorway in an external wall of the building which opens directly into the fire control room from a road or open space; or

a pressurisation system that only serves the fire control room, and—

is installed in accordance with AS 1668.1, except airflow rates nominated by clause 10.3 are replaced with not less than 30 air changes per hour, as though the room is a fire-isolated stairway; and

is activated automatically by operation of the fire alarm, or sprinkler system complying with Specification 17, installed in the building and manually by an over-riding control in the room; and

has fans, motors and ductwork that form part of the system but not contained within the fire control room protected by enclosing construction with an FRL of not less than 120/120/120; and

has any electrical supply to the fire control room or equipment necessary for its operation connected to the supply side of the main disconnection switch for the building.

(2) No openable devices, other than necessary doorways, pressure controlled relief louvres and windows that are openable by a key, must be constructed in the fire control room.

Changed since NCC 2022. See NCC 2022 Volume One S19C11, or show what changed.

(1) A fire control room must be ventilated by — … control room, and — is installed in accordance with AS 1668.1 1668.1, except airflow rates nominated by clause 10.3 are replaced with not less than 30 air changes per hour, as though the room is a fire-isolated stairway; and is … building and manually by an over-riding control in the room; and provides a flow of fresh air through the room of not less than 30 air changes per hour when the system is operating and any door to the room is open; and has fans, motors and ductwork that form part of … a key, must be constructed in the fire control room.